Troubleshooting Meter Communications Issues

Are you struggling with communication issues between your meter and logging software? You're not alone! Many users face challenges that can stem from simple configuration errors or power outages. In our latest guide, we share essential troubleshooting tips, from checking local meter power to ensuring your IP address settings are correct. Discover how to effectively ping your meters, connect locally, and even address potential DHCP conflicts. Don't let communication failures disrupt your operations—empower yourself with the knowledge to resolve these common issues and keep your power monitoring systems running smoothly! Read on for expert insights and solutions.

The most common failure of metering systems is a loss of communications between the meter and the logging software running on a central server or computer. Even with new installations, configuration issues often prevent the meter communications connection.

Tip 1. Check the Meter Locally

Power outages or scheduled maintenance can cause previously connected meters to lose their connection. If you are experiencing connection issues following such events, check to ensure your meter still has control power. Meter control power for many Power Quality meters requires a backup power supply (UPS) control power or battery bus DC control power connection to ensure the PQ meter can fully capture waveforms and high-speed logs during a power outage.

If your installation used a small “point of use” UPS inside the switchgear to carry the meter load during the outage, check it as the most likely failure point. Trusting an expensive PQ meter to be carried by a cheap “point of use” UPS during an outage is the number one way to cause a communication failure. Find these small UPS units and get rid of them.

Tip 2. Ensure the IP Address Programmed into the Meter is Complete

The second most common problem if for new meter installations – do you have the complete IP address programmed? 

A complete address is:

IP Address – 192.168.1.70 

Subnet Mask -255.255.255.0

Gateway – 192.168.1.1.

Many facility networks subdivide the network into smaller sections called subnets. In these cases, the Subnet Mask and Gateway addresses are critical to connecting with the meter across the network.

Tip 3. Ping Meters from the Command Prompt 

The Command Prompt (aka Windows command-line interface) enables you to ping the meter’s IP address from the server, or the server from the meter.


As shown in the image below, right-click on the Windows Start icon on the bottom left of your home screen and select Run.

a screenshot of the start menu on a windows computer .
a screenshot of a windows command prompt window
a screenshot of a command prompt window showing pinging 192.168.1.5

Often, though, the ‘Ping’ command will not be successful – below is an example of an unsuccessful ping of the meter’s address (192.168.1.5), but a successful ping of the Gateway address (192.168.1.254).

If the Ping command is unsuccessful, you will need to work with your IT department to check the network settings on the network equipment (switches or routers) between the meter and the power monitoring server.

Tip 5. Connect Locally to the Meter

Verify the meter is powered up by going to the physical location. Additionally, check the IP address settings using the local display, and connect using an Ethernet patch cable from a laptop.

NOTE – You must configure your laptop IP address to be on the same network as the meter itself.

Below is an example of how to reset your laptop’s “Internet Protocol Version (TCP/IPv4)” address from the default of “Obtain an IP address automatically” to a specific IP address by checking the “Use the following IP address” selection.

a screenshot of a computer 's network and internet settings
Tip 6. Check the meter IP address from a Web Browser

Occasionally, after a power outage, another device (like a printer) may use Dynamic Host Configuration Protocol (DHCP) to steal the meter’s assigned IP address. There are advantages and disadvantages to using DHCP for devices in the field.

The expected result for opening a meter IP address from a web browser is shown below:

Web Page Example:

a computer screen with a schneider electric logo on it
a computer screen shows the status of a dcp l2540dw series printer
Tip 7. Check another connected meter on the system to ensure your Web Browser is appropriately configured

Corporate networks often have Proxy servers enabled. This may block device communication. There are various methods to check for this setting, depending on what browser you are using. For more information on methods for specific browsers, feel free to contact us.

Tip 8. If the meter itself has been without control power it may lose the Ethernet settings due to inadequate internal batteries.

When communicating settings are lost, it is an irritant to reprogram it locally. While you are there, please be sure to test the configuration memory by disconnecting control power for about a minute. If the meter loses the communication settings again, the meter’s onboard BIOS battery will need to be replaced.

Who We Are

At Applied Power Technologies, Inc. (APT), we pride ourselves on our customer service. These are the most common failure modes for meters and the number one cause of service calls for APT from our customers.

Are you still experiencing issues? For more information regarding communication, issues, feel free to reach out to us by phone, email, or web at the link below.

Share the Post:

Related Posts

What the New ASHRAE/PNNL/NEMA Data Center Framework Means for Facilities Teams

The AI Data Center Energy Performance Framework from ASHRAE is a pivotal tool for facilities teams managing data center infrastructure. With electricity demand from data centers expected to surge by 17% in 2025 and double by 2030, a comprehensive energy management approach is vital. This framework combines thermal management, electrical systems, and best practices to address the complete lifecycle of energy management. As demands for accountability grow, implementing this framework is crucial for compliance and sustainability. Learn how to tackle these challenges effectively.

Read More

Your IR Scanning Program Is Compliant — Until It Isn’t

For decades, annual infrared thermography inspections were merely a best practice — but as of January 1, 2023, they are now a mandatory requirement under NFPA 70B. With the stakes higher than ever, facilities teams face challenges like scheduling around load requirements and managing safety concerns during energized work. Fortunately, there’s a better way. APT’s SwitchMon® solution offers continuous, automated monitoring of electrical systems, providing real-time visibility and proactive alerts for developing faults. Discover how this innovative approach not only ensures compliance but also enhances operational efficiency and reduces risks. Ready to transform your compliance strategy?

Read More

This site uses Cookies for the best experience.

By clicking “Accept All Cookies”, you agree to the storing of cookies on your device.